NETYS PR 1700-3300 VA

NETYS PR (1700-3300 VA)

High performance protection on rack or tower
Single/single phase UPS from 1700 to 3300 VA - Rack/Tower

The solution for

• Professional and IT equipment
• Servers and networking devices
• CAD/ Graphic workstations with monitors and peripherals
• Control systems

Advantages

A secure and professional supply continuity

• Ideal solution for protecting small servers, networking devices and peripherals.
• Assures service continuity to critical applications.
• Designed for professional applications: the sinevawe inverter technology assures full compatibility with any kind of load and power supply.

Tailored to IT networking

• The space and time-saving tower/rack conversion option means it can be installed easily either in tower mode or inside standard 19” rack cabinets depending on the user’s needs.

Simple to install

• No configuration needed on first startup.
• Compact footprint (2U/89 mm) for installation in rack cabinets.
• Attractive design for visible installation in offices.
• USB port and HID protocol as standard for direct interfacing with Windows systems®, without the need for additional specialist software.

Protection for your data line

• Integrated NTP protection for LAN/ADSL connection against the risk of data line overvoltage.

Meets practical needs

• Optional battery extension modules (EBM) to meet all back-up time requirements, even after installation.
• Clear and uncluttered LCD interface, with buzzers that immediately indicate the operating status of the UPS, even for less specialist users.
• Simplified maintenance and Battery `hot swap’, without closing down other applications.

Easy to use and to integrate

• Wide range of communication protocols available in options (including JBUS, TCP/ IP and SNMP) for integration into LAN networks or building management systems (BMS)
• Easy connections to the applications (depending on power) via 8 or 8+1 IEC 320 (IT standard) sockets.
• Load segmentation function to prioritize loads and manage critical situations.
• EPO (Emergency Power Off) emergency stop.
• RS232 advanced connections for the management of the power supply and local/ remote shutdown of applications.

  • Standard and option features

  • Technical Data

     

    UPS and internal batteries

     

    NETYS PR RT + 1 (NPR-B1700-RT) + 2 (NPR-B1700-RT)
    1700 VA 22 min 42 min

    NETYS PR RT + 1 (NPR-B3300-RT) + 2 (NPR-B3300-RT)
    2200 VA 37 min 72 min
    3300 VA 22 min 43 min

     


    Connections

     

    1. Fan / air vents
    2. EPO Emergency Power Off
    3. USB serial port
    4. RS232 serial port
    5. Connector for external battery extension

    6. UPS output sockets (2 segments)
    7. NTP protections (RJ45)
    8. Slot for optional communication boards
    9. Input socket
    10. UPS full power output socket





     


    Control panel

     

    1. On / Off
    2. Load present
    3. Load level (5 steps)
    4. General Alarm
    5. Battery fault / Replace the battery
    6. Overload
    7. Battery capacity
    8. Normal mode / Battery mode (flashing)
    9. Automatic Voltage / Regulation active
    10. Configuration
    11. Programmable outlets
    12. Input value
    13. UPS test / Buzzer off
    14. Navigator button
    15. Enter

     

     

    Technical data

     

    Sn 1700 VA 2200 VA 3300 VA
    Pn 1350 W 1800 W 2700 W
    Input / output 1/1  
    Input
    Rated voltage 230 V
    Voltage tolerances 161 V ±4% (selecting wide mode) -276 V ±4%
    Rated frequency 50 / 60 Hz with automatic selection
    Mains connection IEC320-C14 (10 A) IEC320-C20 (16 A)
    Output
    Automatic Voltage Regulation (AVR) The AVR increases (boost 1) the output voltage by 14%
    when the input voltage drops below 90% of the nominal value.
    The AVR decreases (bucks) the output voltage by 12%
    when the input voltage rises above 106% of the nominal value.
    Rated voltage 230 V ±5%
    Rated frequency 50/60 Hz ±0.1%
    Power factor  0.9
    @ 1500 VA
    0.9
    @ 2000 VA
    0.9
    @ 3000 VA
    Wave form Sine wave
    Protection Normal Mode: overload (110% for 3 minutes)
    Battery Mode: overload (110% for 30 seconds); shortcircuit protected
    Sockets 8 (10 A) x IEC 320 8 (10 A) x IEC 320
    1 (16 A) x IEC 320
    Batteries
    Type Sealed lead-acid maintenance free - expected life 3/5 years
    Back-up time (1) 6 min 8 min 6 min
    Communication
    Interface RS232 - USB
    Ethernet adapter NET VISION (TCP/IP & SNMP) optional card
    Local communication software  Local View
    Data line protection NTP data line suppressor: RJ45 10 Base T
    UPS Cabinet
    Dimensions W x D x H 440 x 436 x 87 mm 440 x 608 x 87 mm
    Weight 18 kg 28.2 kg 31.5 kg
    Standards
    Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
    EMC IEC/EN 62040-2, AS 62040.2
    Product declaration CE, RCM (E2376)

     (1) @ 75% of load