NETYS PR 100-1500VA

NETYS PR (1000-1500 VA)

High density, compact power protection on rack
Single/single phase UPS from 1000 to 1500 VA - Rack 1U

Applications

• Professional and IT equipment
• Servers and networking devices
• CAD / graphic workstations with monitors and peripherals
• Control systems

Advantages

A professional UPS

• Designed for professional environments, protection against power cuts and over voltage is ensured by Line Interactive technology with Automatic Voltage Regulation (AVR).

An installation adapted to the networking environment

• NETYS PR rack provides high power density (1U - 45 mm) which conserves valuable space in the rack for other equipment.
• Can be easily installed in 19” and 23” Rack cabinets, depending on the user’s needs. The UPS is provided with rails and mounting accessories.

Adapted connections

• Easy connections to the applications via 4 IEC 320 (IT standard) sockets.

Data line protection

• With RJ45 connector.

Communication with the computer system

• RS232 or USB advanced connections for the management of the power supply and local / remote shutdown of applications.
• Advanced diagnostics and remote control via various protocols and user environments: JBUS, HID, SNMP, TCP / IP.

  • Standard and option features

  • Technical Data

     

    Connections

     

    netys_095_a.jpg

    1. Slot for optional communication boards
    2. Input protection
    3. Network Transient Protector
    4. Output sockets (IEC 320 10 A)
    5. Main input socket (IEC 320)
    6. USB Port
    7. RS232 serial port
    8. DIP switches

     

     

    Control panel

     

    1. ON-OFF button
    2. Test / Alarm reset button
    3. Power ON
    4. Overload
    5. Battery mode
    6. Service
    7. Load segment 2
    8. Load segment 1

     

     

     

    Battery hot-swap

     

    Battery can be hot-swapped without having to shut down the connected equipment.
    Battery can be replaced from the front without removing and disconnecting the UPS.
    Battery check system and replacement indicator.

     

     

     

    Included

     

    1. Mounting bracket
    2. M3 x 6 bracket screws
    1. Rear Hold-Down Bracket
    2. Rail assembly
    3. Assembly Wing Nuts
    4. Wing nut for rear Hold-down bracket

     

     

     

    Technical data

     

    Sn 1000 VA 1500 VA
    Pn 670 W 1000W
    Input / output 1/1  
    Input
    Rated voltage 230 V (default), 220 V, 230 V, 240 V selectable
    Rated frequency 50/60 Hz auto-sensing
    Output
    Rated voltage 230 V
    Rated frequency 50/60 Hz
    Sockets 4 x IEC 320 (10 A)
    Data line protection NTP data line suppressor: RJ45 10 Base T
    Batteries
    Type Sealed lead-acid maintenance free - expected life 3/5 years
    Back-up time (1) 12 min
    Communication
    Interfaces RS232 - USB
    Local communication software Local View
    UPS Cabinet
    Dimensions W x D x H 440 x 578 x 44.5 mm
    Weight 21 kg 23 kg
    Standards
    Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
    EMC IEC/EN 62040-2, AS 62040.2
    Product declaration CE, RCM (E2376)