Modular UPS MODULYS XS

MODULYS XS

The ultimate modularity for the most critical environments
Modular UPS from 2.5 to 20 kVA/kW

Designed with no single point of failure, the MODULYS XS offers high availability and redundant power supply to very critical applications.
With its flexible modularity providing seamless and risk-free power scalability up to 20 kW, the MODULYS XS range is the ideal solution for unscheduled site upgrades or incremental power evolutions. The installed power can be increased up to 20 kW by adding hot-swap plug-in power modules for incremental steps of either 2.5 kW or 5 kW.

The solution for

• Small data centres
• Edge data centres
• Branch office
• Computer networks
• Telecom & media nodes
• Light industrial applications
• Transportation control/signals

Advantages

Fully modular system

• Pluggable and hot-swapped power module with system’s self-setting during installation.
• All the modules can be swapped without switching to external manual bypass.
• Hot swappable battery module designed to be installed with power module in the same UPS enclosure.

‘Forever Young’ concept

• Eliminates end-of-life criticality.
• Module compatibility guaranteed for 20+ years.
• Allows for the implementation of future module technology.

Totally redundant design

• N+1, N+X redundancy level.
• Totally independent power modules to avoid any single point of failure.
• Real selective module disconnection with galvanic separation.
• Distributed parallel control.

Enhanced serviceability performance

• Fast & safe maintenance based on hot-swap modules.
• Designed for concurrent maintenance.

 

  • Standard and option features

  • Technical Data

    UPS System
    Slot 9 6 4 3
    Power [Sn] up to 20kVA up to 15kVA
    Power [Pn] up to 20kW up to 15kW
    Power factor 1
    Number of power modules 4 3
    Input/Output X/1
    Redundant configuration N+x
    Input
    Rated voltage 230V 1ph+N (±20%), 400V 3ph+N (±20%)
    Frequency 50/60Hz ±10%
    Power factor >0.99
    Output
    Voltage 230V (1ph) ±3% (can be set 208/220/240V)
    Frequency 50/60Hz ±2% (±0.1% in battery mode)
    Overload 110% for 1 minutes, 130% for 10 seconds, 200% for 5 cycles
    Bypass
    Voltage rated output voltage ±15%
    Frequency 50/60Hz ±2% (configurable for GenSet compatibility)
    Efficiency
    Online double conversion mode up to 92.8%
    Environment
    Ambient temperature 0 to 40°C (15 to 25°C for maximum battery life)
    Relative humidity 0 to 95% without condensation
    Maximum altitude 2000m without derating
    UPS cabinet
    Display 7” touch 3.5”
    Dimensions W x D x H (mm) 550 x 635 x 1460 550 x 635 x 1060 449 x 570 x 708 449 x 570 x 575
    Weight (empty cabinet) (kg) 120 90 50 44
    Colour RAL 7016
    Degree of protection IP20
    Standards
    Safety IEC 62040-1: 2017 (CB Report)
    EMC IEC 62040-2: 2005
    Product declaration CE, RCM (E2376), UKCA, EAC

    Longer back-up time available on demand.