sharys_27_b_pro_jpg

SHARYS IP system

Rugged, reliable DC power solution
Power station 24/48/108/120 V from 60 to 200 A

The SHARYS IP series have been designed with the objective of reliable DC supply.

Advantages

A modular and flexible range

• Expandable according to future requirements by adding additional rectifier modules.

Reliability and robustness

• Robust steel frame.
• Degree of protection IP30.
• PCB tropicalisation as standard.
• Microprocessor control.
• Intelligent rectifier cooling.
• Battery safe thanks to the end of discharge protection (option).
• Limited thermal stress and longer life of the components.

Total Costs of Ownership (TCO)

• High efficiency up to 93%: low energy consumption, low heat dissipation.
• Sinusoidal current absorption with power factor close to one: low conductor heat dissipation and no plant oversize.
• Easy to install.
• Reduced maintenance costs.
• Process continuity with hot-swap capabilities (replacement of modules without any power interruption).

Easy, user-friendly operation

• Front mimic panel with clear working status indication.
• Digital control and monitoring of the rectifier modules.
• Adapted to be used with different types of battery technologies.
• Wide choice of communication interfaces: Dry contact, MODBUS RTU, SNMP (with NET VISION option).

 

  • Standard and option features

  • Technical Data

     

     

      System IS 4 modules System IX 3 modules
    Input
    Rated voltage 230 V 1ph + N
    400 V 3ph + N
    400 V 3 ph
    Voltage Tolerance ± 20% @ 100% Pn up to a -50% @ 40% Pn
    Frequency from 47.5 to 63 Hz
    Input transformer - included in standard
    Output
    Rated voltage (V) 24 48 108 120 24 48 108 120
    Rated current (A) 200 200 80 80 150 150 60 60
    Maximum power (kW) 4.8 9.6 8.6 9.6 3.6 7.2 6.5 14.4
    Voltage regulation (V) (1) 21 - 29 42 - 58 95 - 131 105 - 145 21 - 29 42 - 58 95 - 131 105 - 145
    Voltage ripple 50 mVrms 100 mVpp
    Efficiency
    Typical > 90%
    Environnement
    Operating ambient temperature -5 ÷ 45 °C without derating, up to 55 °C with power derating
    Relative humidity 10% to 90%
    Cooling forced with intelligent fan speed control
    RECTIFIER CABINET
    Dimensions W x D x H (2) 600 x 600 x 1925 mm
    Weight (3) 245 kg 305 kg
    Degree of protection IP30
    Color RAL 7012
    Standards
    Safety IEC/EN 61204-7
    EMC EN 61204-3, EN 61000-6-4, EN 61000-6-2
    Performance IEC/EN 61204
    Resistance to vibrations ASTM D999
    Resistance to falls ASTM D5276
    (1) Output voltage variation depends on the recharging voltage and on the end of the discharging voltage settings (typically 1.13 Vn with mains present and  battery charged, 0.90 Vn when batteries are completely discharged).
    (2) Height depends on accessories and backup time.
    (3) Without batteries